Rainwater Pipe Size Calculation for Flat Roof Drainage

Answer three questions about your flat roof and see how many outlets it needs and how big the pipes below them should be. The full BS EN 12056-3 working sits underneath for designers to check.

Free to use, no sign-up. Last reviewed 23 November 2026 by THK Roofing.

Flat roof rainwater calculator

Step 1 of 3

What size is the flat roof?

Measure it as if you were looking down on a plan: the length times the width, in square metres.

Not sure? Set the roof area calculator to a flat roof and it gives you this figure.

How does water leave the roof?

Pick the picture that matches. Most small flat roofs drain through a round outlet set into the roof.

Gutters along an edge and siphonic systems are sized differently, so they are outside what this tool covers.

Does the outlet have a grille over it?

A grille, dome or strainer stops leaves getting in. It also halves how much water the outlet can take. Most outlets have one.

More options for roofers

We start at 0.022, the highest Category 1 figure in the UK, so the answer errs on the safe side. Use the figure for your site from the UK National Annex to BS EN 12056-3.

The share of rain that runs off. Use 1.0 for a normal waterproof roof and the maker's figure for a green roof.

Leave at 1.0 unless your specification asks for more. The rainfall category already allows for risk.

Walls rising above the roof shed rain onto it. Half their area, up to 10m high, is added.

35mm has traditionally been accepted on flat roofs laid to falls. Check the laps and upstands sit above it.

Outlet shape

A tapered outlet narrows like a funnel. The shape decides the smallest pipe that can go below it.

Where the outlet maker publishes tested capacities, use those in place of these equations.

Your drainage sizes

Preliminary sizing only. A competent drainage designer must check the final design.

Start with the size of the flat roof.

Sizes show up after your third answer. There is no button to press and nothing to sign up for.

A rainwater pipe size calculation for flat roof drainage starts with the heaviest burst of rain the roof is designed for and ends with the number of outlets and the size of pipe below each one. The calculator above follows BS EN 12056-3, the standard Approved Document H points to for flat roofs. It shows its working at every step.

Preliminary sizing only. Use the tool to plan a roof or to sense-check a design. A competent drainage designer must check the final scheme against BS EN 12056-3 and against the outlet maker's tested capacities.

What the calculator works out

In a short, heavy storm, rain lands on the roof faster than at any other time. The tool turns the size of the roof into a flow in litres per second, then works out how many outlets it takes to carry that flow away without the water getting too deep. It finishes with the smallest pipe each outlet can drain into. If your roof drains through sunken boxes or slots in a parapet wall, it sizes those openings instead.

Rainwater pipe size calculation for flat roof outlets, step by step

  1. Choose the rainfall. Take the design rainfall intensity for the site from the UK National Annex to BS EN 12056-3. For Category 1 it runs from 0.010 litres per second per square metre in the north of Scotland to 0.022 in London and East Anglia.
  2. Find the effective area. Use the plan area of the flat roof, plus half the area of any walls that shed rain onto it, up to 10 metres above the roof.
  3. Work out the flow. Multiply the rainfall by the effective area and by the run-off coefficient, which is 1.0 for a normal waterproof roof.
  4. Check one outlet. Work out what one outlet carries at the design water depth, halving it if a grating is fitted. Divide the flow by that figure and round up to get the number of outlets.
  5. Size the pipe. Find the bore that carries the flow at each outlet, then check it is at least two thirds of a tapered outlet's top diameter.

Worked example: a 60m² flat roof

Take a 60m² flat roof with no walls above it, designed at 0.022 litres per second per square metre. The design flow is 0.022 × 60 = 1.32 litres per second.

A 100mm tapered outlet with a grille carries 0.5 × 100 × 351.5 ÷ 7,500 = 1.38 litres per second at a 35mm water depth, so one outlet is enough. Without the grille it would take 2.76 litres per second.

The Wyly-Eaton equation says a 46mm bore would carry 1.32 litres per second. The two-thirds rule for a 100mm tapered outlet raises that to 67mm. The standard's blockage warning then points to a pipe of at least 75mm.

Rainfall intensity and the risk categories

BS EN 12056-3 designs roof drainage for a short, intense storm, normally lasting two minutes. Its UK National Annex gives maps of rainfall intensity for several return periods. Category 1, a one year return period, is normally used for flat roofs, provided the roof is fully watertight and can cope with brief ponding in rarer storms. The highest Category 1 figures are in London and East Anglia, where short summer storms are most intense. Higher categories apply to valley and parapet gutters and wherever an overflow would damage the building or what is inside it.

The old fixed design figure of 75mm per hour came from BS 6367, which has been withdrawn. HR Wallingford's guide to the current standard says it should no longer be used, although it still turns up in online answers.

Why gratings matter

The standard halves the capacity of an outlet fitted with a grating or strainer. A design that assumes open outlets and is then built with grilles will hold water twice as deep as the designer expected, so the calculator asks about the grille before anything else technical. Every 10mm of standing water adds 10kg to each square metre of roof. Long spells of ponding on a flat roof age the waterproofing faster.

Overflows

An overflow decides what happens when an outlet blocks with leaves. It gives a visible warning that the drainage needs clearing, protects the building from flooding and copes with storms rarer than the design event. Size it as a weir with the same equation as a chute and set it to start working before water reaches the upstands, the laps or any door threshold.

Standard rainwater pipe sizes

Plastic rainwater systems for houses are commonly sold in 68mm round and 110mm round sizes, as manufacturers' ranges such as Wavin's Osma show. A 68mm pipe is smaller than the 75mm bore below which BS EN 12056-3 warns of blockage, which is worth bearing in mind under a flat roof outlet that collects leaves. The sizes in the result are minimum internal bores, so choose the next stock size up.

Gutters and siphonic systems

Gutters along a roof edge are sized from their cross-section, length and freeboard under clause 5 of the standard. Siphonic systems run their pipes full and are designed with the maker's own software. Neither is covered by this tool, which deals with gravity outlets, sumps and chutes on flat roofs. For pitched roofs, our roof pitch calculator and roof tiles calculator cover the slopes themselves.

For designers: the full method and every constant

The tool follows BS EN 12056-3:2000, Gravity drainage systems inside buildings, Part 3: Roof drainage, layout and calculation, with its UK National Annexes, using the procedures in HR Wallingford Report SR 620. Page references are to SR 620.

  1. Rainfall. r in l/s per m² from the National Annex maps for the site and risk category. Category 1 is a 2 minute storm with a 1 year return period, from 0.010 to 0.022 (p.6). To convert from mm per hour, divide by 3,600.
  2. Effective area. A = AH + 0.5 × AV, where AV is the exposed wall area draining onto the roof up to 10m above it (pp.9 to 10).
  3. Design flow. Q = r × A × C, with C = 1.0 for impermeable roofs (p.12), multiplied by any safety factor entered.
  4. Circular outlets, Table 7. Weir flow Qo = k × D × h1.5 ÷ 7,500 where h ≤ D/2. Orifice flow Qo = k × D2 × h0.5 ÷ 15,000 where h > D/2. D and h in mm. k = 1.0 for an open outlet and 0.5 with a strainer or grating. D is the top diameter for sharp-edged and tapered outlets and 0.9 × the top diameter for round-edged ones (pp.23 to 24).
  5. Design water depth. 35mm has traditionally been accepted at outlets on nominally flat roofs laid to falls (p.31).
  6. Sumps and chutes. Weir length Lw = 24,000 × Q ÷ h1.5 in mm. A sump is at least the head over its outlet plus 25mm deep. A chute opening stands at least 25mm above the design depth (pp.27 to 33).
  7. Rainwater pipes. Wyly-Eaton, Q = 2.5 × 10−4 × kb−0.167 × d2.667 × f1.667, with kb = 0.25mm and the UK filling degree f = 0.33. That gives 17.4 l/s for a 120mm bore. The bore should be at least two thirds of the outlet's top diameter. The standard also points out the risk of blockage below DN 75 (p.34).

Gutters, horizontal collector pipes and siphonic pipework are outside the scope of the tool.

To talk through the drainage on a particular flat roof, you can get in touch with us.

Flat roof drainage questions

How do you calculate rainwater flow from a flat roof?

Multiply the effective roof area in square metres by the design rainfall intensity in litres per second per square metre and by the run-off coefficient. A 60 square metre roof at 0.022 gives 1.32 litres per second.

What size downpipe do I need for a flat roof?

Size it for the flow at each outlet with the Wyly-Eaton equation, then check it is at least two thirds of a tapered outlet's top diameter. BS EN 12056-3 also warns that pipes below 75mm bore are prone to blockage.

How many outlets does a flat roof need?

Divide the design flow by what one outlet carries at the design water depth and round up. A grating halves an outlet's capacity, so allow for it if one is fitted.

What rainfall intensity is used for flat roofs in the UK?

BS EN 12056-3 takes it from the maps in its UK National Annex. Flat roofs are normally designed for Category 1, a two minute storm with a one year return period, which runs from 0.010 to 0.022 litres per second per square metre.

Should flat roof drainage still be designed at 75mm per hour?

No. That fixed figure came from BS 6367, which has been withdrawn. HR Wallingford's guide to BS EN 12056-3 says it should no longer be used. Use the intensity for your site from the National Annex.

Does a grating reduce the capacity of a roof outlet?

Yes. BS EN 12056-3 uses an outlet coefficient of 0.5 for an outlet with a grating or strainer against 1.0 for an open one, which halves its capacity.

Is this calculator enough to design my roof drainage?

No. It gives preliminary sizing for planning and checking. A competent drainage designer should check the final design against BS EN 12056-3, using the outlet maker's tested capacities where they are published.

Sources and method

Made by THK Roofing Ltd, a roofing contractor registered in England and Wales, company number 13986959.